Ethylene oxide is toxic even at very low concentrations and easily forms flammable mixtures. At a sterilization facility, air treatment is what keeps the pollutant from leaving the plant.
CONTENTS
IN SHORT
Ethylene oxide (EtO) is widely used to sterilize medical devices that cannot withstand high temperature or humidity. It is toxic even at very low concentrations and, within a certain range, forms a flammable mixture with air. Ventilating or diluting is not enough.
That is why, here, the air treatment installation is not an add-on to the process. It is the decisive safety barrier between the industrial process and the plant’s surroundings.
The amount of EtO in the exhaust gases fluctuates widely during degassing and aeration. The vacuum pump discharge produces short, high peaks, while the aeration chambers emit smaller amounts, but continuously.
If that stream goes straight to the catalytic reactor, without dampening, the result is thermal shocks, incomplete conversion and operation close to the lower explosive limit (LEL).
A water column with recirculation absorbs EtO during peaks and releases it when the concentration drops. This stage does not remove the ethylene oxide; it only stabilizes the stream going to the next one. Peak loads are reduced, there are fewer occasions of approaching the LEL and the reactor temperature is more stable.
In the reactor, the EtO is oxidized to CO₂ and water. The reaction is exothermic, so a heat exchanger recovers part of the energy and reduces fuel consumption. Preheating at the inlet (gas, electric or steam) keeps the catalyst within its optimum temperature range.
There is one condition: the gas may only contain compounds of carbon, hydrogen, nitrogen and oxygen, with no catalyst poisons. Under those conditions, efficiency exceeds 99%. We explain when a catalyst is not a good idea in the comparison of RTO, RCO and biofilters.
Some scrubbers that work with sulfuric acid or glycol produce a liquid effluent that then has to be managed. Catalytic oxidation converts EtO into stable gaseous products without additional reagents. That means simpler regulatory compliance, less handling of chemicals and no fixed disposal costs.
An extraction fan placed after the reactor keeps the whole installation under slight negative pressure, which limits fugitive emissions. The next layers of protection are integrated LEL measurement and automatic temperature control.
The treatment installation has to be designed together with the whole process:
The system has to handle both the high peaks from degassing and the steady, lower load from aeration.
Whether the solution is viable, and what it costs, depends on this data.
Evening out the concentrations hydraulically and combining this with catalytic oxidation makes it possible to meet strict emission limits without secondary waste. But efficiency does not depend only on the reactor and the catalyst: process stabilization, heat management, tightness and good integration with the sterilization stages also count.
More than 99%, if the gas only contains compounds of carbon, hydrogen, nitrogen and oxygen and carries no catalyst poisons.
It absorbs EtO during peaks and releases it when the concentration drops. It does not remove the pollutant, but it evens out the stream, so the reactor does not suffer thermal shocks and the installation operates well away from the lower explosive limit.
No. Unlike some scrubbers using sulfuric acid or glycol, catalytic oxidation produces no liquid waste: the EtO is converted into CO₂ and water.
AUTHOR
WIZZUM engineering teamWe design and commission wastewater and gas treatment installations for industry, from benchmarking and FEED engineering to start-up.
NEED HELP?
27/02/2024
Efficiency, operating temperature, energy use and maintenance of the three most widely used technologies, and how to choose the right one for your plant.
Read the article →
06/06/2023
Are eco-friendly alternatives always better? A technical view without greenwashing.
Read the article →
13/08/2024
Properties of ethylene oxide and ways to treat wastewater containing it.
Read the article →
OFFICE
Avda. Cabrera, 36
08302 Mataró (Barcelona), Spain
info@wizzum.com
© 2026 Wizzum. All rights reserved.